The letters name the insulation and its ratings: T is thermoplastic, X cross-linked, R rubber; H is 75 C and HH 90 C; W means wet locations; N a nylon jacket; and -2 means 90 C in wet locations too. THWN-2 is therefore thermoplastic, nylon jacketed, 90 C wet or dry.

The letters
LetterMeaning
TThermoplastic insulation (PVC)
XCross-linked polymer insulation, which does not soften with heat
RRubber (thermoset) insulation
HRated 75 C
HHRated 90 C
WRated for wet locations
NNylon outer jacket
-2Rated 90 C in wet locations as well as dry
U, SEUnderground; service entrance (as in USE)
Common types, NEC Table 310.4(1)
TypeMaximum temperatureWhere it may be used
TW60 CDry and wet locations
THW75 CDry and wet locations
THHW90 C dry, 75 C wetDry and wet locations
THHN90 CDry and damp locations
THWN75 CDry and wet locations
THWN-290 CDry and wet locations
XHHW90 C dry, 75 C wetDry, damp and wet locations
XHHW-290 CDry and wet locations
RHH90 CDry and damp locations
RHW-290 CDry and wet locations
USE-290 CDry and wet locations, underground service entrance
SIS90 CSwitchboard wiring only