Wire ampacity chart (NEC Table 310.16)
Under NEC Table 310.16, 12 AWG copper carries 20 A at 60 C, 25 A at 75 C and 30 A at 90 C, but NEC 240.4(D) still limits it to a 20 A breaker. Most breakers and lugs are rated 75 C, so the 75 C column is the usual limit over 100 A, and the 60 C column at 100 A or less unless the equipment is marked 75 C (110.14(C)).
| Size | Copper 60 C | Copper 75 C | Copper 90 C | Aluminum 60 C | Aluminum 75 C | Aluminum 90 C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | |||
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
| 600 kcmil | 350 | 420 | 475 | 285 | 340 | 385 |
| 700 kcmil | 385 | 460 | 520 | 315 | 375 | 425 |
| 750 kcmil | 400 | 475 | 535 | 320 | 385 | 435 |
| 800 kcmil | 410 | 490 | 555 | 330 | 395 | 445 |
| 900 kcmil | 435 | 520 | 585 | 355 | 425 | 480 |
| 1000 kcmil | 455 | 545 | 615 | 375 | 445 | 500 |
- The table assumes not more than three current-carrying conductors in a raceway, cable or directly buried, at an ambient temperature of 30 C. More conductors or more heat call for the adjustments in 310.15; the ampacity calculator applies them.
- NEC 240.4(D) caps overcurrent protection at 15 A for 14 AWG copper, 20 A for 12 AWG copper and 30 A for 10 AWG copper, and at 15 A and 25 A for 12 and 10 AWG aluminum.
- NM-B and UF-B cable are held to the 60 C column (334.80, 340.80). Dwelling services and main feeders may use the 83 percent rule of 310.12.