Battery cable size calculator

At 12 V a 3 percent drop is only 0.36 V, so battery cable is sized by voltage drop long before ampacity matters. Enter the one-way distance; the calculator counts the run out and back.

Conductor
System

Result

0.62 V, 5.13 percent. Smallest size for this load at or under 3.00 percent: 1 AWG

Voltage drop, 4 AWG
0.62 V, 5.13 percent
At the load
11.38 V
Smallest size for this load at or under 3.00 percent
1 AWG

Shop 1 AWG wire

Drop by size
SizeDrop (V)Drop (%)Max load (A), 75 C
18 AWG15.90132.50cord size
16 AWG9.9883.17cord size
14 AWG6.2852.3315
12 AWG3.9633.0020
10 AWG2.4820.6730
8 AWG1.5612.9750
6 AWG0.988.1865
4 AWG0.625.1385
3 AWG0.494.08100
2 AWG0.393.23115
1 AWG, meets target0.312.57130
1/0 AWG0.242.03150
2/0 AWG0.191.61175
3/0 AWG0.151.28200
4/0 AWG0.121.01230
250 kcmil0.100.86255
300 kcmil0.090.72285
350 kcmil0.070.61310
400 kcmil0.060.53335
500 kcmil0.050.43380
600 kcmil0.040.36420
700 kcmil0.040.31460
750 kcmil0.030.29475
800 kcmil0.030.27490
900 kcmil0.030.24520
1000 kcmil0.030.22545

Uses stranded conductor resistance at 75 C from NEC Chapter 9, Table 8. Single phase and DC: 2 x I x R x L. Three phase: 1.732 x I x R x L. AC reactance, which adds a little on large conductors in steel conduit, is not included. Max load comes from the ampacity column you pick, with 14, 12 and 10 AWG copper held to 15, 20 and 30 A (12 and 10 AWG aluminum to 15 and 25 A). NM-B and UF-B are held to the 60 C column. A continuous load needs 125 percent, and more than three conductors or high heat lower it.

Use it to size a run, then check the size against your local code or with a licensed electrician.