4-4-4 SEU Aluminum Cable

Aluminum service entrance cable for the run from the meter to the panel and for subpanel feeds.

Per foot at 50 ft$1.68/ft

Product image of SER/SEU aluminum, representative of the family

Choose colors and lengths

Color: Gray

By the foot: cut to your length, final sale. Spool: the factory put-up, returnable uncut, never more per foot than a cut. Cut wire is final sale.

Skip to Add to cart
    • $1.68/ft
      Ships by Fri, Oct 9
Total $0.001 line

Ships by Fri, Oct 9

For an order placed now. Orders after 12 PM ET, and on weekends and holidays, count from the next business day.

You get a tracking number by email the day it ships.

Free UPS Ground shipping from $499 to the lower 48. A reel over 150 lb ships by freight, charged in the cart.

Cut wire is final sale. Uncut spools can come back within 30 days for a 15 percent restocking fee. Returns policy

Questions about this wire?

Request a callback

Leave your number and a rep calls you back.

At a glance

Ampacity65 A (NEC Table 310.16, 75 C column)
Largest breaker65 A, or the next standard size up where NEC 240.4(B) allows. With 60 C rated terminals (the NEC 110.14(C) default at 100 A or less unless the equipment is marked 75 C) it is 55 A.
Voltage drop at 100 ft6.60 V, 2.8 percent at 65 A and 240 V single phase
Run length for 3 percent dropAbout 105 ft one way at 65 A and 240 V
Outside diameter0.505 in

Questions about this size

What breaker can 4-4-4 SEU Aluminum Cable go on?
Its ampacity is 65 A (75 C column of NEC Table 310.16). The breaker can be that size, or the next standard size up where NEC 240.4(B) allows it. Derate first for more than three current-carrying conductors or high ambient heat. With 60 C rated terminals (the NEC 110.14(C) default at 100 A or less unless the equipment is marked 75 C) it is 55 A.
How far can I run it before voltage drop is a problem?
At 65 A on a 240 V single phase circuit, about 105 ft one way keeps the drop at 3 percent, the figure an informational note to NEC 210.19(A) suggests for branch circuits. Try other loads in the voltage drop calculator.
Can it be buried directly in the ground?
No, and not in underground conduit either: NEC 338.12(A) does not permit SE cable underground, with or without a raceway. Use URD or USE-2, or wet-rated conductors in conduit.
Can I buy it by the foot?
Yes, cut to length in whole feet from 50 ft, or on 500 ft spools. Cut wire is final sale; uncut spools can be returned within 30 days.

Full specifications

TypeSER/SEU aluminum
Gauge4-4-4
Conductors3
Conductoraluminum
Strandingstranded
Nominal O.D.0.505 in
Ampacity, NEC Table 310.16, 75 C column65 A
Sold by the footFrom 50 ft to 5,000 ft, in whole feet
Standard spools500 ft
Ships in1 to 2 business days from the order day

Insulation, ratings, listing and weight are confirmed from the manufacturer's sheet with your quote.

Spec sheet on request.