Voltage drop calculator

Enter the circuit and the one-way length of the run. You get the drop for the size you pick and the smallest size that stays at or under your target.

Conductor
System

Result

13.00 V, 10.83 percent. Smallest size for this load at or under 3.00 percent: 6 AWG

Voltage drop, 12 AWG
13.00 V, 10.83 percent
At the load
107.00 V
Smallest size for this load at or under 3.00 percent
6 AWG

Shop 6 AWG wire

Drop by size
SizeDrop (V)Drop (%)Max load (A), 60 C
18 AWG52.4043.67cord size
16 AWG32.8427.37cord size
14 AWG20.6817.23cord size
12 AWG13.0010.8315
10 AWG8.166.8025
8 AWG5.124.2735
6 AWG, meets target3.232.6940
4 AWG2.031.6955
3 AWG1.611.3465
2 AWG1.281.0675
1 AWG1.010.8485
1/0 AWG0.800.67100
2/0 AWG0.640.53115
3/0 AWG0.500.42130
4/0 AWG0.400.33150
250 kcmil0.340.28170
300 kcmil0.280.24195
350 kcmil0.240.20210
400 kcmil0.210.18225
500 kcmil0.170.14260
600 kcmil0.140.12285
700 kcmil0.120.10315
750 kcmil0.110.09320
800 kcmil0.110.09330
900 kcmil0.090.08355
1000 kcmil0.080.07375

Uses stranded conductor resistance at 75 C from NEC Chapter 9, Table 8. Single phase and DC: 2 x I x R x L. Three phase: 1.732 x I x R x L. AC reactance, which adds a little on large conductors in steel conduit, is not included. Max load comes from the ampacity column you pick, with 14, 12 and 10 AWG copper held to 15, 20 and 30 A (12 and 10 AWG aluminum to 15 and 25 A). NM-B and UF-B are held to the 60 C column. A continuous load needs 125 percent, and more than three conductors or high heat lower it.

Use it to size a run, then check the size against your local code or with a licensed electrician.