Voltage drop calculator

Enter the circuit and the one-way length of the run. You get the drop for the size you pick and the smallest size that stays at or under your target.

Conductor
System

Result

7.92 V, 6.60 percent. Smallest size for this load at or under 3.00 percent: 8 AWG

Voltage drop, 12 AWG
7.92 V, 6.60 percent
At the load
112.08 V
Smallest size for this load at or under 3.00 percent
8 AWG

Shop 8 AWG wire

Drop by size
SizeDrop (V)Drop (%)Max load (A), 60 C
18 AWG31.8026.50cord size
16 AWG19.9616.63cord size
14 AWG12.5610.4715
12 AWG7.926.6020
10 AWG4.964.1330
8 AWG, meets target3.112.5940
6 AWG1.961.6455
4 AWG1.231.0370
3 AWG0.980.8285
2 AWG0.780.6595
1 AWG0.620.51110
1/0 AWG0.490.41125
2/0 AWG0.390.32145
3/0 AWG0.310.26165
4/0 AWG0.240.20195
250 kcmil0.210.17215
300 kcmil0.170.14240
350 kcmil0.150.12260
400 kcmil0.130.11280
500 kcmil0.100.09320
600 kcmil0.090.07350
700 kcmil0.070.06385
750 kcmil0.070.06400
800 kcmil0.060.05410
900 kcmil0.060.05435
1000 kcmil0.050.04455

Uses stranded conductor resistance at 75 C from NEC Chapter 9, Table 8. Single phase and DC: 2 x I x R x L. Three phase: 1.732 x I x R x L. AC reactance, which adds a little on large conductors in steel conduit, is not included. Max load comes from the ampacity column you pick, with 14, 12 and 10 AWG copper held to 15, 20 and 30 A (12 and 10 AWG aluminum to 15 and 25 A). NM-B and UF-B are held to the 60 C column. A continuous load needs 125 percent, and more than three conductors or high heat lower it.

Use it to size a run, then check the size against your local code or with a licensed electrician.