Ordering too little wire stops a job; ordering too much leaves you with a partial spool you paid full price for. A quick takeoff before you order gets you close, and knowing when to buy a cut and when to buy a full spool saves money on top of that.
Step 1: measure the route, not the distance
Measure the path the wire actually takes: up the wall, across the ceiling, around beams and down to the device. A run that is 40 ft in a straight line is often 60 ft by the raceway. For a conduit job, measure the conduit, then add each vertical drop.
Step 2: add the extra at each end
NEC 300.14 requires at least 6 in. of free conductor at every box where it is spliced or connected, and where the box opening is less than 8 in. across, at least 3 in. has to reach outside the opening. In practice most electricians leave 8 to 12 in. at a device box and more at a panel, where the conductor has to reach its breaker or lug.
A simple rule: add 2 ft per box and 3 to 6 ft at the panel, more for a large panel where the breaker is far from the entry.
Step 3: multiply by the number of conductors
In conduit, each conductor is a separate wire. A 120/240 V circuit with two hots, a neutral and a ground is four conductors, so a 60 ft conduit run needs 4 x (60 ft + ends) of wire. Order by color:
| Conductor | Color | Length for a 60 ft run with 6 ft of ends |
|---|---|---|
| Hot | Black | 66 ft |
| Hot | Red | 66 ft |
| Neutral | White | 66 ft |
| Ground | Green | 66 ft |
With cable such as NM-B, UF-B or SER, you order the cable once, because the conductors are inside it.
Step 4: add a margin
Add 10 percent to the total for waste, a pull that goes wrong and small changes on site. On long pulls with many bends, add more.
Cut to length or full spool?
| Situation | Better choice |
|---|---|
| One run, one or two colors | Cut to length |
| Several runs of the same size and color | Full spool |
| Large conductors for a single feeder | Cut to the exact length |
| Stock for the van or the shop | Full spool |
| A color you rarely use | Cut to length |
Where a product is sold both ways, its page prices the cut and each spool size, so you can compare them before you order. Two things to keep in mind:
- Cut to measure cable is final sale. It is cut for your order and cannot be returned, so measure twice. Uncut spools can be returned under the terms on our returns page, unless the line says final sale.
- A cut adds a business day to the ship date shown on the product page.
Worked example
A 100 A feeder from a main panel to a subpanel in a detached shop. The conduit route is 85 ft, with 6 ft of ends at the main panel and 4 ft at the subpanel. The feeder is two hots, a neutral and an equipment ground.
- Length per conductor: 85 + 6 + 4 = 95 ft
- Add 10 percent: about 105 ft
- Order: 105 ft each of two hot conductors and the neutral, plus 105 ft of the ground size
The sizes come from the load calculation and NEC Table 310.16; for a comparison of copper and aluminum for a feeder like this, see aluminum vs copper feeders. On a run this long, check voltage drop too with the voltage drop calculator.
Shop by the foot or by the spool
- 12 AWG THHN/THWN-2 and 10 AWG in every common color
- 2 AWG XHHW-2 aluminum and 1/0 XHHW-2 aluminum for feeders
- 12/2 NM-B and 12/2 UF-B
The allowances above are common practice, not code requirements, except where a section of the NEC is cited. Your job conditions and local rules decide the final numbers.