Electrical wire color code: what the NEC requires and what is convention

Published Sep 30, 2026

The NEC only fixes the colors of two conductors: the grounded conductor (the neutral in most systems) and the equipment grounding conductor. Everything else is convention, local amendment or the owner's spec. Knowing which is which saves arguments at inspection.

What the NEC requires

ConductorRequired identificationWhere in the NEC
Grounded conductor (neutral)White or gray insulation, or three continuous white or gray stripes on another color other than green200.6(A)
Equipment grounding conductorBare, green, or green with one or more yellow stripes250.119
Ungrounded (hot) conductorsAny color except white, gray or green310.6(C) and 200.7
High leg of a 4-wire deltaOrange, or another effective marking, at every point where the neutral is also present110.15 and 230.56

Larger sizes can be re-marked. A grounded conductor 4 AWG and larger may be identified at each termination with white or gray tape or paint instead of colored insulation (200.6(B)). An insulated equipment grounding conductor 4 AWG and larger may be re-identified with green tape or paint at each end and wherever it is accessible (250.119(A)). That is why large feeders are often all black.

Posting is required. Where a building has branch circuits from more than one voltage system, NEC 210.5(C) requires the identification method for each system to be documented and posted at each panelboard, or otherwise made available.

The common conventions

These are not in the NEC, but they are what most electricians and many specs expect.

SystemPhase APhase BPhase CNeutralGround
120/240 V single phaseBlackRedWhiteGreen or bare
120/208 V three phaseBlackRedBlueWhiteGreen or bare
277/480 V three phaseBrownOrangeYellowGrayGreen or bare

A few details:

  • White on 120/208 V and gray on 277/480 V keeps the two neutrals apart in a building that has both.
  • Some jurisdictions and owners write these conventions into their own rules. Check the local amendments and the project spec.
  • Orange is phase B on 277/480 V by convention, and the NEC marking for the high leg of a 120/240 V four-wire delta (orange or another effective marking, 110.15). Confirm what the building already uses before you add circuits.

Switch legs, travelers and DC

  • Switch legs are often red or black. A white conductor in a cable can be used as a switch loop feed only if it is re-identified and it supplies the switch, not the return (200.7(C)(1)).
  • Three-way travelers are commonly red and black in 14/3 or 12/3 cable, or any agreed pair in conduit.
  • For DC systems such as PV and battery circuits, NEC 210.5(C)(2) and Article 690 cover polarity identification. Red for positive and black for negative is common, but follow the posted scheme.